After replacement of the control PC board, operation does not start with an malfunction “LC” displayed.
Operation was initiated without setting the horsepower.
Set the horsepower based on the service manual or information of repair of parts.
Setting the horsepower corresponding to the capacity of the model is needed after replacing the control PC board of VRV.