To Access Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as follows:
With torque wrench: Finger tighten and torque cap per table 1.
Without torque wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/6 turn
clockwise.
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:
With Torque Wrench: Finger tighten and then torque cap per table 1.
Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/12 turn
clockwise.