Daikin VRV – RSXY8, 10K and RSXYP8, 10KJ Electric and Functional Components

Schematic Diagram of Refrigerant

No. Parts name Symbol (Electric symbol) Function
Outdoor unit sensor Outdoor thermistor Ta R1T (Th1) In heating operation standby due to outdoor temperature (forcedly thermostat-off at 27°C or higher), influence to defrost condition.
Heat exchanger thermistor Tb R2T (Th2) In heating operation, used for detection of defrosting
Discharge pipe thermistor Tdi, Tds R31T (Th3-1) R32T (Th3-2) Used for protection control of discharge pipe temperature
Suction pipe thermistor Ts R4T (Th4) In heating operation, used for superheated degree (SH = Ts – Te) control of outdoor electronic expansion valve
High-pressure sensor Pc, Tc (SENPH) Used for high pressure control and for compressor capacity control in heating operation. Although the pressure (Pc) is detected, controlling should be based on the equivalent saturation temperature (Tc).
Low-pressure sensor Pe, Te (SENPL) Used for low pressure control and for compressor capacity control in cooling operation. Although the pressure (Pe) is detected, controlling should be based on the equivalent saturation temperature (Te).
Indoor unit sensor Suction air thermistor Tr R1T (Th1) Used for thermostat control and compensation of electronic expansion valve control.
Liquid pipe thermistor Tl R2T (Th2) Used for superheated degree (SH = Tg – Tl) control in cooling operation and freeze-up prevention control. Used for subcooled degree (SC = Tc – Tl) control during heating operation and cancellation of hot start (34°C) control.
Gas pipe thermistor Tg R3T (Th3) Used for subcooled degree (SH = Tg – Tl) control in cooling operation.
Components of outdoor unit A Inverter compressor INV (MC1) Used to conduct the capacity control (constant Te control in cooling, constant Tc control in heating) with inverter.
B STD compressor STD (MC2) Used to conduct the capacity control with compressor using commercial power supply and inverter compressor (delayed start).
C Receiver Making constant supply of liquid refrigerant to liquid receiver and evaporator (expansion valve). Storing excessive refrigerant
D Accumulator Gas-liquid separator avoiding direct suction of liquid refrigerant to compressor.
E Outdoor unit heat exchanger Working as condenser in cooling operation and as evaporator in heating operation (air-cooled)
F Outdoor unit electronic expansion valve Y1E (20E) Controlling so as to keep superheated degree (SH = Ts – Te) constant (basically 5°C)
G Hot gas bypass solenoid valve Y2S (20RP) Used for pressure equalizing and low-pressure protection in no operation.
H Injection solenoid valve Y3S Y4S (20RT) Conducts protection control with discharge pipe temperature (Tdi, Tds) and discharge superheated degree (Tdi, Tds – Tc)
I Check valve Prevents refrigerant from backword flow in operation only with inverter compressor. (Prevention of standard compressor start with deferential pressure)
J Four way valve Y1R (20S) Making selection of cooling / heating cycle (energized coil for heating)
Components of indoor unit K Indoor unit heat exchanger Heat exchanger works as evaporator in cooling operation and as condenser in heating operation. (Air cooled type)
L Indoor unit electronic expansion valve Y1E (20E) Used for superheated degree (SH = Tg – Tl) control in cooling operation, and for subcooled degree (SC = Tc – Tl) control during heating operation. Avoiding liquid collection, by setting the valve as minute opening (240 pls) in heating thermostat-off (when compressor is on).