Gas and liquid leg shutoff Figure 10-18 illustrates a flooded floor unit suitable for operation down to ?70°F (?57°C). The gas-pressure-powered valve used in this circuit has a solenoid pilot operator. This provides positive action with gas or liquid loads … Continue reading

16. January 2011 by admin
Categories: Evaporators | Tags: | Leave a comment

HVAC Flooded-ceiling blower

Top hot-gas feed Figure 10-16 shows a modification of the system shown in Fig. 10-15. In the system shown in Fig. 10-16, top-fed hot defrost gas forces the evaporator fluid directly to the bottom of the large surge drum. The … Continue reading

16. January 2011 by admin
Categories: Evaporators | Tags: | Leave a comment

HVAC Flooded-ceiling evaporator—liquid leg shutoff

Bottom hot-gas feed Figure 10-14 illustrates a flooded-ceiling evaporator. Upon initiation of the defrost sequence, the hot gas solenoid (Number 1) is opened. Gas flows to gas-powered check valve, isolating the bottom of the surge tank from the evaporator. The … Continue reading

16. January 2011 by admin
Categories: Evaporators | Tags: | Leave a comment

HVAC Flooded-gas leg shutoff

The system shown in Fig. 10-13 is similar to that shown in Fig. 10-12. However, the liquid leg of the evaporator dumps directly into the surge drum without a relief valve. In this system, valve C is a defrost regulator. … Continue reading

16. January 2011 by admin
Categories: Evaporators | Tags: | Leave a comment

HVAC Flooded Liquid Systems

Figure 10-12 shows a flood-gas and liquid leg shutoff (top hot-gas feed) system. Here, the gas-powered valve is used on both ends of the evaporator. It is a gas-powered check valve. At defrost, the normally closed type-A pilot solenoid is … Continue reading

16. January 2011 by admin
Categories: Evaporators | Tags: | Leave a comment

HVAC Direct Expansion with Top Hot-Gas Feed

In the evaporator shown in Fig. 10-10, when the defrost cycle is initiated, the hot gas is introduced through the hot-gas solenoid valve to the manifold. It then passes through the balancing glove valve and the pan coil to a … Continue reading

16. January 2011 by admin
Categories: Evaporators | Tags: , | Leave a comment

HVAC Evaporator Defrost cycle

When the three-position selector switch is turned to defrost, solenoid valve A and pilot-solenoid valve D close as hot-gas valve C and evaporator-pilot valve B open. This allows hot gas to enter the evaporator. Valve D now acts as a … Continue reading

16. January 2011 by admin
Categories: Evaporators | Tags: | Leave a comment

HVAC Evaporator Cooling cycle

During the normal cooling cycle controlled by a thermostat, as room temperature rises above the high setting on the thermostat there is a need for refrigeration. Liquid solenoid (valve A) and the built-in pilot (valve D) open, allowing refrigerant to … Continue reading

16. January 2011 by admin
Categories: Evaporators | Tags: | Leave a comment

Valves used in direct-expansion systems

The pilot solenoid (valve B) is a 1/8 in. ported solenoid valve that is direct operated and suitable as a liquid, suction, hot gas, or pilot valve at pressures to 300 lb. Solenoid valve A is a one-piston, pilot-operated valve … Continue reading

16. January 2011 by admin
Categories: Evaporators | Tags: | Leave a comment

HVAC Direct-expansion systems

Figure 10-7 shows a high temperature system [above 32°F (0°C)] with no drip-pan defrost. During the normal cooling cycle, controlled by a thermostat, the room temperature may rise above the high setting of the thermostat. This indicates a need for … Continue reading

16. January 2011 by admin